5: Facp Data Bus; Nfw-100X; Firewarden-100-2 - Honeywell NOTIFIER NFC-50/100 Instruction Manual

Table of Contents

Advertisement

Installation
2.6.5 FACP Data Bus

NFW-100X

The FACP communicates with the NFC-50/100 over the ANN-BUS annunciator bus. Wiring must be connected between the primary
ANN-Bus terminal TB9 or the secondary ANN-BUS terminal TB10 on the FACP and Terminal TB13 on the NFC-50/100 panel.

FireWarden-100-2

The FireWarden-100-2 FACP communicates with the NFC-50/100 over the ACS or ANN-BUS annunciator link. Wiring must be con-
nected between Terminal TB9 on the FACP and Terminal TB13 on the NFC-50/100 panel.
NFC-50/100
34
NFC-50/100
Figure 2.19 Connection for NFW-100X to NFC-50/100
to other ACS/ANN
devices
Figure 2.20 Connection for FireWarden-100-2 to NFC-50/100
to other ANN
devices
TB9 or TB10
A
B
A
TB9
TB10
NFW-100X
ANN
ACS
TB8
OUT+ IN+ OUT- IN-
FireWarden-100-2
Notifier FirstCommand Series Manual — P/N LS10001-001NF-E:H 1/8/2018
B
A
B
+
-
SLC
SHIELD
SLC
SLC
SLC
TB9
TB10
ACS
B+ A+ B- A-
A
B
Output Circuits