2.1 Mounting Options

The cabinet may be semi-flush or surface mounted. The cabinet mounts using three key slots at the top of the backbox and two additional
0.250" diameter holes located at the bottom.
Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry, vibration-free area where extreme tem-
peratures are not encountered. The area should be readily accessible with sufficient room to easily install and maintain the panel. Locate
the top of the cabinet approximately five feet above the floor with the hinge mounting on the left. Determine the number of conductors
required for the devices to be installed. Sufficient knockouts are provided for wiring convenience. Select the appropriate knockout(s) and
pull the required conductors into the box. Note that knockouts are also located on the back of the cabinet. All wiring should be in accor-
dance with the National and/or Local codes for fire alarm systems. Refer to Figure 2.4 for knockouts that cannot be used.

2.2 Backbox Installation

CAUTION: STATIC SENSITIVE COMPONENTS
!
THE CIRCUIT BOARD CONTAINS STATIC-SENSITIVE COMPONENTS. ALWAYS GROUND YOURSELF WITH A
PROPER WRIST STRAP BEFORE HANDLING ANY BOARDS SO THAT STATIC CHARGES ARE REMOVED FROM THE
BODY. USE STATIC SUPPRESSIVE PACKAGING TO PROTECT ELECTRONIC ASSEMBLIES.

Removing the Dress Panel

1.
Open the door and lift the door off the pin hinges.
2.
Loosen the two (2) screws that secure the dress panel to the backbox. Then, lift up to swing the dress panel open.
3.
Disconnect the ground wire from the dress panel.
4.
Unplug the cable on the display board at J2. This is the connection to the main control board on the chassis.
5.
Lift the dress panel up and gently pull the lower hinge out of the backbox. Gently pull down to remove the top hinge. Store the dress
panel in a safe place.
22

Section 2: Installation

unplug cable
dress panel
lift up
,
pull out,
slide down to remove
Figure 2.1 Dress Panel Removal
Notifier FirstCommand Series Manual — P/N LS10001-001NF-E:H 1/8/2018
ECC-MCB-PCA
Rev.
J12
loosen screws
TB15
J9
RTZM
disconnect
earth ground

Hide quick links: