Programmed Activation by FACP
VeriFire Tools Programming
Map ACS Address 1 to M. Assign desired panel points (SLC devices, zones, logic zone, releasing zones, etc) to ACS Points in User Map
1.
ACS Point 40 is assigned to all speaker circuits. If an addressable device programmed to ACS Point 40 is activated, the message will be
generated to all speaker circuits. If the newly activated point is programmed to activate a message with a higher priority, the higher pri-
ority message will be generated to all circuits.
Panel Programming
If VeriFire Tools is not used and Group M is programmed at the panel, Zone 00 (general alarm) will be mapped to A1p11 and A1p40. A
general alarm will play message 1 and activate an all-call on the FirstCommand. VeriFire Tools must be used for speaker and circuit and
message control.
IMPORTANT! Messages have a priority scheme with Message 1 having the highest priority and Message 14 having the lowest priority.
The highest priority message will always be generated over all activated speaker circuits.
Notifier FirstCommand Series Manual — P/N LS10001-001NF-E:H 1/8/2018
FireVoice Speaker
Circuit/Message Assignment
NFC Message 0
NFC Message 1
NFC Message 2
NFC Message 3
NFC Message 4
NFC Message 5
NFC Message 6
NFC Message 7
NFC Message 8
NFC Message 9
NFC Message 10
NFC Message 11
NFC Message 12
NFC Message 13
NFC Message 14
All Speaker Circuits - All-Call (1-24)
Speaker Circuit 1
(on NFC)
Speaker Circuit 24
(on NFC)
Table 3.5 Speaker Circuit and Message Assignments
Panel ACS Point
1 - 9 (Do Not Use)
No Message (Message Off)
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25 - 39 (Do Not Use)
40
41
64
Programming
69