5.1 System Requiring up to 50 Watts of Audio Power

1.
Install backbox and chassis assembly as described in Section 2, "Installation", on page 22.
2.
Connect laptop or PC to Ethernet port (J2) and launch the web-based programming utility.
3.
Configure the NFC-50/100 for Single Zone operation, if individual speaker circuit control is not required. The factory default
setting is Single Zone output control. Refer to Section 3, "Programming", on page 51.
4.
Record any new voice messages as described in Section 4, "Operating Instructions", on page 70.

5.2 System Requiring Up to 100 Watts of Audio Power

1.
Install backbox, chassis assembly, and NFC-BDA-25/70V and circuit boards as described in Section 2, "Installation", on page 22.
2.
Connect laptop or PC to Ethernet port (J2) and launch the web-based programming utility.
3.
Configure the NFC-50/100 for Single Zone operation. Refer to Section 3, "Programming", on page 51.
4.
Record any new voice messages as described in Section 4, "Operating Instructions", on page 70.

5.3 System Requiring Greater Than 100 Watts of Audio Power

1.
Install backbox and chassis assembly as described in Section 2, "Installation", on page 22.
2.
Connect the external Audio Riser and external Data Bus (for All-Call) cabling between the NFC-50/100 and NFC-125DA and/or
NFC-50DA panels.
3.
Connect laptop or PC to Ethernet port (J2) and launch the web-based programming utility.
4.
Configure the NFC-50/100 for Single Zone operation. Refer to Section 3, "Programming", on page 51.
5.
Record any new voice messages as described in Section 4, "Operating Instructions" on page 70.
6.
Program the FACP to operate with the NFC-50/100 per the FACP manual.
– Enable the ACS-BUS serial link or ANN-BUS serial link.
– Assign audio zones where applicable (see Section 3.6, "Programmed Activation by FACP", on page 64).
– Assign message numbers (1 - 5) where applicable (refer to Section 3.6, "Programmed Activation by FACP", on page 64).
7.
Connect the external Audio Riser and NFC external Data Bus cabling between the NFC-50/100 and the NFC-125DA and/or NFC-
50DA.
Notifier FirstCommand Series Manual — P/N LS10001-001NF-E:H 1/8/2018

Section 5: Getting Started

77

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Notifier nfc-50/100eNotifier firstcommand seriesNotifier firstcommand nfc-50/100Notifier firstcommand nfc-50/100e

Table of Contents