Appendix B: Wiring Requirements - Honeywell NOTIFIER NFC-50/100 Instruction Manual

Table of Contents

Advertisement

Connecting external system accessories to the NFC-50/100 main circuits must be carefully considered to ensure proper operation. It is
important to use the correct type of wire, wire gauge and wire run length per each circuit. Refer to the following table to specify wire
requirements and limitations.
NOTE: If an SLC loop is to be run in conduit with NFC-50/100 Notification Appliance Circuits, the risk of encountering problems can be
greatly reduced by using twisted, shielded cable on the SLC and NACs.
Circuit Type
CMD1-CMD2
TB4, TB5: polarity reversal
CMD1-CMD2
TB4, TB5: contact closure
CMD3-CMD8
TB6-TB8: contact closure
speaker circuits
TB20, TB21
ECC-CE6 speaker circuits
TB1 - TB6
external data bus: TB12
external audio riser: TB22
external operator interface power:
TB24
NAC output: TB19
speaker volume control override:
TB23
night ring input: TB16
external audio input
TB5 (on display board)
MNS active, AC loss, and trouble
output relays: TB1 - TB3
auxiliary power: TB17
1 Refer to NEC Standards.
2 Twisted, shielded wire is recommended for maximum protection against EMI and AFI emissions and susceptibility.
3 Must also meet NFPA 72 Standards for minimum and maximum sound levels.
NOTE: Wire to wire short circuit trouble = zero ohms.
Open circuit trouble = infinite ohms.
Ground fault trouble = zero ohms to ground.
82

Appendix B: Wiring Requirements

Wire Type & Limitations
untwisted/unshielded,
twisted/shielded, see note
untwisted/unshielded,
twisted/shielded, see note
untwisted/unshielded,
twisted/shielded, see note
untwisted/unshielded,
twisted/shielded, see note
untwisted/unshielded,
twisted/shielded, see note
twisted/shielded
twisted/shielded
untwisted/unshielded,
twisted/unshielded
untwisted/unshielded,
twisted/unshielded
untwisted/unshielded,
twisted/unshielded
untwisted/unshielded,
twisted/unshielded
twisted/shielded
untwisted/unshielded,
twisted/shielded, see note
untwisted/unshielded, see note
Table B.1 Wiring Requirements
Notifier FirstCommand Series Manual — P/N LS10001-001NF-E:H 1/8/2018
Maximum Distance (feet)
depends on trigger circuit,
1
9-32 VDC, 1.6 mA
max loop impedance 200 ohms
1
max loop impedance 200 ohms
1
determine using Lite-Calcs utility
2
3
see note
determine using Lite-Calcs utility
2
3
see note
max loop impedance 13.2 ohms
max loop impedance 13.2 ohms
max loop impedance 13.2 ohms
refer to Section 2.6.3 , max loop
impedance 120 ohms
max loop impedance 120 ohms
max impedance 30 K ohms
max loop impedance 100 ohms
depends on the panel monitoring
1
these outputs
1
distance set by 4 VDC max line
drop
Wire Gauge
(terminals support)
12-18 AWG
12-18 AWG
12-18 AWG
12-18 AWG
12-18 AWG
12-18 AWG
12-18 AWG
12-18 AWG
12-18 AWG
12-18 AWG
12-18 AWG
12-18 AWG
12-18 AWG
12-18 AWG