Main Menu - User Programming
3.2.3 Address Assignment
Remote Microphone / Operator Console Address Assignments
Any combination of up to eight (8) remote consoles (NFC-LOC, NFC-RPU, and NFC-RM) can be used in the system. Odd numbered
addresses are not selectable. Addresses must be sequential, even numbers. Identify which consoles are installed at addresses 4, 6, 8, 10,
12, 14, 16, and 18 as either Local Operator Console or Remote Microphone. Note that the NFC-RPU and NFC-RM are both considered
remote microphones. Refer to Section 2.14, "Addressing External Data Bus Devices" for information on dipswitch settings. Note that
Address 2 is reserved for the POC.
Mic Gain is the microphone's transmitting "volume control". The gain number is automatically entered when a remote console is pro-
grammed.
Speaker Circuit Address Assignment
Notifier FirstCommand Series Manual — P/N LS10001-001NF-E:H 1/8/2018
Figure 3.6 RM/Console Address Assignments
Figure 3.7 Remote Amplifier Address Assignments
Programming