The absolute value of the MSS clock is not used to correlate scanner data to
scanner position; however, it is convenient if the time stamps on the scanner
logs correspond to the QCS server alarm page times. Resetting the MSS time
reboots all EDAQs on the scanner. This is to avoid potential interlock
failures when the local EDAQ clocks jump forward or backward. The
scanner should be off-sheet during any clock settings
MSS Troubleshooting
No MSS – RAE communication
If the MSS Summary Page (MSS Setup Diagnostic tab) does not have a green
light next to the appropriate MSS, or the MSS monitor page does not show '
, then the MSS is not communicating with the Experion MX system.
DR events'
1. Verify the MSS has DC power (green LEDs at power connector on all
models). And the LAN indicator is blinking indicate network
connection to server is running. If power indicator is off, check incoming
AC supply to MSS and power to MSS is available. Replace MSS if power
is available but DC power is off.
Figure 18 MSS Set time menu
process