Wiring Zones (cont'd)
When this wiring mode is employed, only one detector which can report fault conditions should be connected
to the zone. A maximum of two detectors or contacts of any type should be connected to a zone when this
mode is selected. It is recommended that zone cable lengths are kept below 100m in this configuration.
NOTE: The recommended maximum cable run from a zone to a detector is 500 metres in all other configu-
rations.
Option 02 - 1k
Tamper S/C
0 - 800
Low Res
800 - 900
Normal
900 - 1200
High Res
1200 - 1300
Fault
-
Masked
1300 - 12000
Open
12000 - infinity
Option 10 - 1k Fault End-Of-Line
The wiring in Figure 2-12 should be used if the mode is end-of-line. Fault and mask indications can only be
signalled if the detector has seperate fault and mask indications.
Zone
Figure 2-12. Option 10 - End of Line Zone/Detector wiring
When this wiring mode is employed, only one detector which can report fault conditions should be connected
to the zone. A maximum of two detectors or contacts of any type should be connected to a zone when this
mode is selected. It is recommended that zone cable lengths are kept below 100m in this configuration.
NOTE: The recommended maximum cable run from a zone to a detector is 500 metres in all other configu-
rations.
Option 04 - 2k2
0 - 1800
1800 - 2000
2000 - 2500
2500 - 2700
-
2700 - 12000
12000 - infinity
Table 2-8. End of Line Zone Resistance and Conditions
Alarm N/C
Tamper N/C
Galaxy Dimension Installer Manual
Option 06 - 4k7
Option 08 - 5k6
0 - 3700
0 - 1400
3700 - 4200
1400 - 2800
4200 - 5500
2800 - 8400
5500 - 6500
8400 - 9800
-
6500 - 19000
9800 - 19000
19000 - infinity
19000 - infinity
3k
Fault N/C
100 m
2-14
Option 10 -1k Fault
0 - 800
800 - 900
900 - 1200
1200 - 1300
-
1300 - 4500
4500 - 19000
19000 - infinity
12k
Anti-Mask N/C
1k