Honeywell Galaxy Dimension Series Installer Manual page 188

Hide thumbs Also See for Galaxy Dimension Series:
Table of Contents

Advertisement

56 - Communications (cont'd)
1 = Status
To modify the trigger, select the required trigger type using the A and B keys and press the ent key. To
program the status to On press 1, to set it to Off press 0. Press the ent key to save the programming and
return to the previous menu level.
Programming the SIA Format with Groups Enabled
If groups have been enabled on the system (refer to option 63 = OPTIONS), then the SIA format menu alters
slightly; an additional level is added.
1 = Trigger Events
On selecting the SIA level the keypad displays 1 = Trigger Events; press the ent key to display the first
trigger event; the keypad shows the trigger, the trigger status and the groups assigned.
1 = Status
To modify the trigger select the required trigger type using the A and B keys and press the ent key. The
1 = Status option is then displayed. If the status requires to be modified, press the ent key. To program
the status to On press 1, to set it to Off press 0. Press the ent key to save the programming and return to
the previous menu level.
2 = Groups
If groups have been enabled on the system (refer to option 63 = OPTIONS), then groups can be assigned
to the events. This means that the events have to occur in assigned groups before they are signalled. Press
the A key, the keypad displays 2 = Group Settings and then press the ent key; the status of the groups
assigned to the trigger is displayed. If the group has Y below it, then this event occurring in this group is
signalled. If N is displayed, then the event is not signalled for that group. To toggle the status of a group,
enter the group number. When all the groups have been assigned press the ent key to save the program-
ming and return to the previous menu level.
Cross Group Confirmation
Confirmed outputs (and channels in DTMF format, option 56.1.1.1) will activate for alarms across groups
as long as both groups concerned have been assigned to that output or channel. In the point ID signalling
formats (SIA, Microtech and Contact ID), confirmed signals will be transmitted across groups that share the
same account number. For example, in option 56.1.1.2 (SIA), it is possible to select a different account
number for each group on the system. Group 1 and group 2 can both be programmed with the same account
number. If there is a single activation in group 1 then a single intruder activation in group 2, within the con-
firmed time window, a confirmed alarm signal will be transmitted for group 2.
Multi-group systems
The larger Galaxy panels have 32 groups; these are displayed on the keypad in blocks of eight groups,
sub-divided into A, B, C and D:
Use the A or B key to select the required group (A1–D8). When the end of a block is reached the next
block of eight groups is selected, press keys 1–8 to toggle the status of the relevant group in the current
block; press the ent key to accept the selection.
Galaxy Dimension Installer Manual
6-114