Ethernet Virtual Loop - Network Dedicated To Access Control - Honeywell MPA2 Installation Manual

Access control unit
Hide thumbs Also See for MPA2:
Table of Contents

Advertisement

4.6 Ethernet Virtual Loop - Network Dedicated to Access Control

Figure 17: Ethernet Virtual Loop - Network Dedicated to Access Control
DIP Switch Settings:
SW3: ON
SW9: ON
SW1 &10: ON : OSDP
SW1 &10: OFF: Wiegand
SW2: 4-8: OFF
1. Router must provide DHCP service.
Note:
2. The Router has not been evaluated by UL.
MPA2 Access Control Unit Installation Guide, Document 800-25395 - B
Terminal
MPA2
Primary
MPA2
Panel
(Secondary)
EG
EG
DIP Switch Settings:
SW3: OFF
SW9: ON
SW1 &10: ON: OSDP
SW1 &10: OFF: Wiegand
SW2: 4-8: OFF
Ethernet Connection with EVL Loop on Dedicated Network
ROUTER
MPA2
NetAXS-123
Panel
Panel
(Secondary)
(Secondary)
DIP Switch Settings:
S1-S5: Panel Address
S6: OFF
S7: OFF
S8-S9: ON: 485 Termination ON
Installing the MPA2 Panels
System Configuration
To NETWORK
CAT 7 S/FTP
NetAXS-123
Panel
(Secondary)
EG
EG
51