System Configuration; Ethernet Connection To Unit's Primary Managing Rs485 Loop - Honeywell MPA2 Installation Manual

Access control unit
Hide thumbs Also See for MPA2:
Table of Contents

Advertisement

Installing the MPA2 Panels

System Configuration

4.0 System Configuration
This section provides wiring diagrams for each of the MPA2 system
configurations.
4.1 Ethernet Connection to MPA2 Primary Managing RS485 Loop
Figure 12: Ethernet Connection
Terminal
RS-485 Multidrop
DIP Switch Settings
SW5-9: Panel Address
SW3: ON: Primary
SW4: OFF: Follow User Configured IP
S1 7-8: ON: 485 Termination ON
DIP Switch Settings
SW5-9: Panel Address
SW6: OFF
SW4: OFF
S1 7-8: OFF: 485 Termination OFF
MPA2
Panel
EG
46
www.honeywell.com
100 BaseT (CAT 7 S/FTP) 328 Ft. Max. (90 m)
NIC
NIC
MPA2
Panel
EG
MPA2
Panel
100 BaseT (CAT 7 S/FTP) 328 Ft. Max. (90 m)
EG
NetAXS-123
Panel
EG
EG
DIP Switch Settings
S1-S5: Panel Address
S6: OFF
S7: OFF
S8 - S9: ON: 485 Termination ON
HUB/SWITCH
HUB/SWITCH
It is
recommended to
Earth Ground (EG)
each NetAXS
enclosure
individually
DIP Switch Settings
SW5-9: Panel Address
SW3: ON: Primary
SW4: OFF: Follow User Configured IP
S1 7-8: OFF: 485 Termination OFF
MPA2
NetAXS-123
Panel
Panel
EG
DIP Switch Settings
S1-S5: Panel Address
S6: OFF
S7: OFF
S8 - S9: ON: 485 Termination ON
SWITCH