Honeywell MZ-PCSV74 Planning, Installation And Service Manual page 16

Table of Contents

Advertisement

2.6.8
Environmental
Operating temperature
Shipping temperature
Storage temperature
Maximum wet bulb temperature 28 °C (82.4 °F)
Operating humidity
Storage humidity
Airborne Contaminants
Copper Reactivity Level
H2S Gas concentration
S02, S03 Gas concentration
+10 °C to +35 °C (50 °F to 95 °F) with a maximum
temperature gradation of 10° per hour.
Note: For Altitudes above 2950 feet , the maximum
operating temperature is derated 1 °F/550 ft.
All temperature ratings shown are for sea level. An
altitude derating of 1 °C per 300 m (1.8 °F per 1,000 ft)
to 3048 m (10,000 ft) is applicable. No direct sunlight
allowed.
-30 °C to 50 °C (-22 °F to 122 °F)
–40 °C to 65 °C (–40 °F to 149 °F)
ATTENTION
All temperature ratings described previously
are for sea level. An altitude derating of 1 °C
per 300 m (1.8 °F per 1,000 ft) to 3048 m
(10,000 ft) is applicable. Direct sunlight is not
allowed.
10% to 80% Relative Humidity with 29 °C (84.2 °F)
maximum dew point
5% to 95% RH with 33 °C (91 °F) maximum dew
point. Atmosphere must be non-condensing at all
times.
ATTENTION
Storing maximum humidity of 95% is based
on a maximum temperature of 45 °C (113
°F). Altitude maximum for storage
corresponds to a pressure minimum of 70
KPa.
Airborne Contaminants < 300 angstroms/month
Copper Reactivity Level < 3 mm3/m3 parts per billion
H2S Gas concentration < 10 mm3/m3 parts per billion
S02, S03 Gas concentration < 1 mm3/m3 parts per
- 16 -
Chapter 2 - Planning

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents