How to Program a Releasing Zone
Relea. Form-C Type Code
NOTE: An output with a relea.form c Type Code requires the following selections: A Releasing
Zone selection (R0-R9); An output circuit mapped to the same Releasing Zone; Switch Inhibit
selected; Non-Silenceable; No Walk Test.
The following contains information needed to program a Release Form-C circuit for an output
.
circuit
Description
An output circuit, configured as a relay, programmed to activate an output by opening or closing a
switch. Typical applications include closing doors and air handlers.
Programming
1.
Select a control module (refer to "Modify or Delete a Point (2=point)" on page 19) to use as a
Releasing Form-C Circuit.
2.
Select the
shown).
3.
Select the Releasing Zone (R0-R9) for your releasing application.
4.
Press the
screen.
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
.
Type Code, as shown in the following example (control module
RELEA
FORM C
PROGRM RELEA.FORM C MODULE ADDR 2M108
Releasing Zone
selection (R5 shown)
Switch Inhibit: I = selected
key to save, then press the
ENTER
Type Code selection:
RELEA
R5 __ __ __ __
I**
key two times to return to the Program Change
ESC
Releasing Applications
.
FORM C
2M108
Walk Test
Selection: * = off
Silenceable: * = off
85