Programming
The Modify Point and Delete Point screens let you edit or delete points for a detector, a monitor or
control module, or NAC. To select a point, follow these steps:
To select
an addressable
detector
an addressable monitor
module
an addressable control
module
a NAC
The next four sections describe how to program the points selected.
Modify an Addressable Detector Point
This section contains a sample detector programming screen, detector default selection, and
instructions for modifying a detector point. Autoprogram default values for a detector are shown:
P R O G R M S M O K E ( P H O T O ) D E T E C T O R A D D R 1 D 1 0 1
12 spaces for extended custom label
Field
Description
Type Code
Detector function
specification -
SMOKE(PHOTO) in example.
Custom
20 character custom label.
Label
20
Do the following
Press
Type the SLC number (1 or 2) and
detector (D) and address (001-159)
Press
Press
Type the SLC number (1 or 2) and module
(M) and address (001-159)
Press
Press
Type the SLC number (1 or 2) and module
(M) and address (001-159)
Press
Press
Type the NAC address (01-04)
Press
Blinking Type Code selection
0 3 _ _ _ _ _ _ _ _ A 8 P 8 A V 1 D 1 0 1
CBE list
(five zones)
Alarm sensitivity level
Pre-alarm sensitivity level
Table 2.2 Detector Program Values
Set as Follows
Press the
or
NEXT
PREVIOUS
Type Code selections. See F.4.2 on page 112 for lists and descriptions.
Change by placing the cursor into the first space of the field using the arrow
keys, then typing the descriptor. DETECTOR ADDR 1D101 is the
autoprogram default custom label for the detector at address 101 on SLC 1.
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
Refer to
"Modify an Addressable Detector
Point" on page 20.
"Modify an Addressable Monitor
Module Point" on page 22.
"Modify an Addressable Control
Module Point" on page 23.
"Modify NAC Points" on page 24.
20-character user-editable custom label (in
this example, autoprogramming has used
the first 19 and left a space at the end.)
SLC address (001-159)
D (detector)
SLC Loop number
Alarm verification setting
Cooperative multi-detector
mode indicator
Selection keys to scroll through valid detector
Basic Program