Programming
Modify an Addressable Monitor Module Point
When you select a point address, the control panel returns a screen that displays information about
the point. Below is an example of information for a monitor module (2M101) in the LCD display:
P R O G R A M M O N I T O R
H A L L W A Y
12 spaces for extended
custom label
Table 2.3 Modifying Monitor Module Programming Selections
Field
Description
Type Code
Monitor Module function specification
-
MONITOR
Custom Label
20 character custom label.
Extended Label 12 character custom label extension.
CBE List
Five zones can be listed - one zone,
Z09, is shown in the example. Up to 4
more could be added to this module.
When finished modifying a point, press the
select another point.
Monitor Module Default Zone Assignments
Listing of the monitor module address range and the default zone assignment for each range:
22
Blinking Type Code selection
W E S T E R N E N T R A N C E A N D
0 9 _ _ _ _ _ _ _ _
Default zone
CBE list
(five zones)
Set as Follows
Press the
in example.
valid monitor module Type Code selections. Lists and
descriptions are in See Table F.2 on page 114.
Change by placing the cursor into the first space of the field
using the arrow keys, then typing the descriptor.
Note: Spaces must be input by the user, including any space
necessary between the custom and extended label fields. An
80-column printout will run the two fields together.
See "Custom Label" above.
Zones can be changed or added to the CBE list by placing the
cursor in the zone field using arrow keys, then typing.
See Table 2.4 on page 22 for defaults.
Table 2.4 Monitor Module Default Zones
Monitor Module Address
01 through 19
20 through 39
40 through 59
60 through 79
80 through 99
100 through 119
120 through 139
140 through 159
20-character user-editable custom label.
2 M 1 0 1
or
Selection keys to scroll through
NEXT
PREVIOUS
key; then press the
ENTER
Zone Default
Z04
Z05
Z06
Z07
Z08
Z09
Z10
Z11
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
Basic Program
SLC address (001-159)
M (module)
SLC number (1 or 2)
or
key to
NEXT
PREVIOUS