Honeywell Notifier NFS2-640/E Programming Manual page 42

Fire alarm control panel
Hide thumbs Also See for Notifier NFS2-640/E:
Table of Contents

Advertisement

Programming
ACS Selection Group P (SLC #1, Modules 65-100 and Detectors 1-14):
Point
1
2
3
to
36
37
38
39
40
63
64
* Pressing the switch button when the Switch Function is "Not Used" will cause the associated LED to stop
blinking. This is a local acknowledgement at the annunciator only: no message is sent to the panel.
NOTE:
1. Point number to Module number relationship is sequential. To determine Point to Module
relationship add 64 to Point number to arrive at Module number.
2. Point number to Detector number relationship is sequential in groups of 2. Since each detector
occupies 2 points, to determine the Point to Detector relationship, count by 2 starting from point
37.
3. This group is only available when UDACT setting is programmed as option 2 and will
automatically be assigned to ACS address 24.
42
Table 2.27 ACS Group P (see note 3)
Type
Red LED
Input
SLC 1, Module 65 Alarm
Input
SLC 1, Module 66 Alarm
Input
SLC 1, Module 67 Alarm
to (see note 1)
Input
SLC 1, Module 100 Alarm
Input
SLC 1, Detector 1 Alarm
Input
SLC 1, Detector 1 Trouble
Maintenance Urgent
Input
SLC 1, Detector 2 Alarm
Input
SLC 1, Detector 2 Trouble
Maintenance Urgent
to (see note 2)
Input
SLC 1, Detector 14 Alarm
Input
SLC 1, Detector 14
Trouble Maintenance
Urgent
Yellow LED
SLC 1, Module 65 Trouble Not Used
SLC 1, Module 66 Trouble Not Used
SLC 1, Module 67 Trouble Not Used
to (see note 1)
SLC 1, Module 100
Trouble
SLC 1, Detector 1 Trouble Not Used
SLC 1, Detector 1 Trouble
Maintenance Alert
SLC 1, Detector 2 Trouble Not Used
SLC 1, Detector 2 Trouble
Maintenance Alert
to (see note 2)
SLC 1, Detector 14
Trouble
SLC 1, Detector 14
Trouble Maintenance Alert
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
Basic Program
Switch Function*
Not Used
Not Used
Not Used
Not Used
Not Used