Basic Program
ACS Selection Group I (SLC #2, Detectors 1-64):
Point
1
2
3
to
64
* Pressing the switch button when the Switch Function is "Not Used" will cause the associated LED to
stop blinking. This is a local acknowledgement at the annunciator only: no message is sent to the panel.
NOTE: Point number to Detector number relationship is sequential; therefore, point 48 is
Detector 048.
ACS Selection Group J (SLC #1, Detectors 65-128):
Point
1
2
3
to
64
* Pressing the switch button when the Switch Function is "Not Used" will cause the associated LED to
stop blinking. This is a local acknowledgement at the annunciator only: no message is sent to the panel.
NOTE: Point number to Detector number relationship is sequential. To determine Point to
Detector relationship add 64 to Point number to arrive at Detector number.
ACS Selection Group K (SLC #2, Detectors 65-128):
Point
1
2
3
to
64
* Pressing the switch button when the Switch Function is "Not Used" will cause the associated LED to
stop blinking. This is a local acknowledgement at the annunciator only: no message is sent to the panel.
NOTE: Point number to Detector number relationship is sequential. To determine Point to
Detector relationship add 64 to Point number to arrive at Detector number
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
Table 2.22 ACS Group I
Type
Red LED
Input
Detector 001 Alarm
Input
Detector 002 Alarm
Input
Detector 003 Alarm
to (see note)
Input
Detector 064 Alarm
Table 2.23 ACS Group J
Type
Red LED
Input
Detector 065 Alarm
Input
Detector 066 Alarm
Input
Detector 067 Alarm
to (see note)
Input
Detector 128 Alarm
Table 2.24 ACS Group K
Type
Red LED
Input
Detector 065 Alarm
Input
Detector 066 Alarm
Input
Detector 067 Alarm
to (see note)
Input
Detector 128 Alarm
Yellow LED
Switch Function*
Not Used
Detector 001 Trouble
Not Used
Detector 002 Trouble
Not Used
Detector 003 Trouble
to (see note)
Not Used
Detector 064 Trouble
Yellow LED
Switch Function*
Detector 065 Trouble
Not Used
Detector 066 Trouble
Not Used
Detector 067 Trouble
Not Used
to (see note)
Detector 128 Trouble
Not Used
Yellow LED
Switch Function*
Detector 065 Trouble
Not Used
Detector 066 Trouble
Not Used
Detector 067 Trouble
Not Used
to (see note)
Detector 128 Trouble
Not Used
Programming