How to Program a Releasing Zone
When an initiating device activates, you must press and hold the Abort Switch or the control panel
will send the command to dump releasing agents when the Delay time (15 seconds shown) expires.
The Abort selection (ULI, IRI, NYC, or AHJ) determines the function of the Abort Switch.
P R G R E L E A S E F U N C T
D E L A Y = 1 5
SYSTEM
NORMAL
Abort station with Abort Switch
and Manual Release lever
B01
Type Code
RELEASE CKT
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
A B O R T = U L I C R O S S = N S O K = 0 0 0 0
Releasing Zone R05 sample programming selections
SYSTEM
ACTIVATED
Monitor
Module with
ABORT SWITCH
Type Code
B02
Type Code
REL CKT ULC
Example: If you program B01-B03 as shown,
these outputs activate at release.
Figure A.3 Example of a Basic Configuration for an Abort Switch
R E L E A S E C O N T R O L
Detector
Detector
R05
B03
Type Code
Type Code
REL AUDIBLE
REL END BELL
Example: If you
program B04 as
shown, this output
activates when the
release is finished.
Releasing Applications
R 0 5
B04
63