Basic Program
ACS Selection
Group
NOTE: Refer to the VeriFire™ Tools programming utility for programming these annunciators.
ACS Selection Group A:
Point
1
2
3
4
5
6
7
8
9
10
11
to
64
*
Pressing the switch button when the Switch Function is "Not Used" will cause the associated LED to
stop blinking. This is a local acknowledgement at the annunciator only: no message is sent to the panel.
NOTE: Point number to Zone number relationship is sequential. To determine Point to Zone
relationship subtract 8 from Point number to arrive at Zone number.
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
Table 2.13 ACS Selection Groups (2 of 2)
Annunciator Display
4
Programmable Annunciator #4
5
Programmable Annunciator #5
6
Programmable Annunciator #6
7
Programmable Annunciator #7
8
Programmable Annunciator #8
9
Programmable Annunciator #9
0
Programmable Annunciator #10
Table 2.14 ACS Group A
Type
Red LED
Input
System Alarm
Output
Not Used
Output
Not Used
Output
Not Used
Output
NAC #1 Active
Input
Security
Input
Not Used
Input
Not Used
Input
Zone 1 Active
Input
Zone 2 Active
Input
Zone 3 Active
to (see note)
Input
Zone 56 Active
Refer to
See Note
See Note
See Note
See Note
See Note
See Note
See Note
Yellow LED
Switch Function
System Trouble
Acknowledge
Signal Silenced
Alarm Silence
Program Mode
System Reset
Supervisory
Drill
NAC Trouble
Control NAC #1
P/A Maint. Alert
Not Used
Low Battery
Not Used
AC Fail
Not Used
Zone 1 Trouble
Not Used
Zone 2 Trouble
Not Used
Zone 3 Trouble
Not Used
to (see note)
Zone 56 Trouble
Not Used
Programming
*
35