Releasing Applications
MANREL DELAY
The following contains information needed to program a Manual Release Delay switch for a
monitor module using the
Description
A monitor module—connected to a UL-listed manual station (such as the Notifier NBG-12LRA)—
used to initiate a manual release with 30-second delay time.
A Manual Release Delay switch overrides the FACP programmed Delay Timer in certain
circumstances, but not the soak timer.
Override Circumstances:
When the Manual Release Delay Switch activates, the control panel replaces the Delay Time
with 30 seconds if the Delay Timer
• is set to more than 30 seconds
• is running, and
• has not counted down below 30 seconds.
NOTE: When the Delay Timer is set to less than 30 seconds, activation of the Manual Release
Delay Switch will invoke the FACP programmed Delay Time if the Delay Timer is not running, or
the FACP programmed Delay Timer countdown time if it is running. Refer to the examples 1
through 5 later in this section.
Multiple monitor modules can be programmed with a
multiple conventional manual release switches on a conventional zone.
How to program
1.
2.
3.
4.
76
Type Code
MANREL DELAY
Select a monitor module (refer to "Modify or Delete a Point (2=point)" on page 19) to use
for the manual release function.
Select the
MANREL DELAY
P R O G R M M A N R E L _ D E L A Y M O D U L E A D D R 2 M 1 0 1
R 5 _ _ _ _ _ _ _ _
Select the Releasing Zone (R0-R9) for your releasing application.
Press the
key to save, then press the
ENTER
Change screen.
Type Code.
MANREL DELAY
Type Code.
Type Code selection:
MANREL
Releasing Zone selection (R5 shown)
key until you return to the Program
ESC
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
How to Program a Releasing Zone
Type Code. They work like
_
DELAY
2 M 1 0 1