Basic Program
Field
Description
Extended
12 character custom label
Label
extension.
CBE List
Five zones can be listed - one
zone, Z03, is shown in the
example. Up to 4 more could
be added to this detector.
Alarm
The alarm sensitivity level,
Sensitivity
with 9 the least sensitive
alarm level and 1 the most
sensitive alarm level.
Pre-alarm
Shows the Pre-Alarm level
level
setting—a number between 0
and 9—as follows:
0 – no Pre-Alarm
1 – self optimizing
2 – most sensitive Pre-Alarm
level
9 – least sensitive Pre-Alarm
level
Cooperative
Indicates the cooperative
Multi-
multi-detector mode (A in the
detector
example).
mode
Alarm
Indicates the alarm
verification
verification setting (V in the
example).
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
Table 2.2 Detector Program Values
Set as Follows
See "Custom Label" above.
Note that spaces must be input by the user, including any space necessary
between the custom and extended label fields. An 80-column printout will
run the two fields together.
Zones can be changed or added to the CBE list by placing the cursor in the
zone field using arrow keys, then typing.
Defaults:
Zone 01 (Heat detectors)
Zone 02 (Ion detectors)
Zone 03 (Photo detectors, Beam detectors)
Zone 04 (Laser detectors)
Zone 05 (Multisensor)
Refer to Table C.2 on page 101 for settings. Select by placing the cursor in
the field using the arrow keys, then either pressing the
keys to make the selection, or typing the value.
Defaults:
A8 (Photo)
A6 (Ion)
A6 (Laser)
A5 (Multisensor)
Refer to Table C.2 on page 101 for settings. Select by placing the cursor in
the field using the arrow keys, then either pressing the
keys to make the selection, or typing the value.
Defaults:
P8 (Photo)
P6 (Ion)
P6 (Laser)
P5 (Multisensor)
Select by placing the cursor in the field using the arrow keys, then either
pressing the
or
NEXT
value.
* = OFF (Default)
A combines the detector's alarm decision with the next address above
B combines the detector's alarm decision with the next address below
C combines the detector's alarm decision with the next address above and
the next address below
Indicates Alarm Verification (V=on, *=off). Select by placing the cursor in the
field using the arrow keys, then pressing the
the selection. Refer to "Interpreting a Detector Status Display or
Maintenance Report" on page 104 for more information on the alarm
verification feature.
Note: Do not use this setting when an alarm activation requires activation of
two or more automatic detection devices.
keys to make the selection, or typing the
PREVIOUS
or
NEXT
Programming
or
NEXT
PREVIOUS
or
NEXT
PREVIOUS
keys to make
PREVIOUS
21