Revolution/Unit time
1.
While Auxiliary Mode Enabled Signal is ON, the counter counts the number of
input pulses for a specified time.
12. Setting method: Set auxiliary mode setting mode to 5 and set Time Setting and
Auxiliary Mode Enabled Signal ON.
13. The Revolution/Unit time Count function is used to count the number of pulses for a
specified time while Auxiliary Mode Enabled Signal is ON.
14. Revolution/Unit time can be derived using the following: a) The number of pulses
updated for a specified time b) The number of pulses per revolution input.
15. The value of RPM is derived using the number of pulses per revolution input with
the time duration set to 1 minute (60000ms).
16. Display during auxiliary mode operation: While Auxiliary Mode Enabled Signal is
ON, it counts the number of input pulses for the unit time with auxiliary mode in
progress. (Figure 19 shows the example where the number of pulses per revolution is
1.)
R200
2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide
May 2010
Figure 19 – Revolution/Unit Time
Honeywell
2. Specifications
2.4. Counter Functions
55