8.1. Error Code
Error code
(Dec)
CH0
CH1
Compared output 1 maximum value exceeded maximum input
32
132
range
Compared output 1 minimum value > compared output1
33
133
maximum value set
34
134
Pulses per revolution range exceeded
35
135
Frequency input mode range exceeded
ATTENTION
196
2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide
Description
If the module status is normal, RUN LED is ON.
If two or more errors occur, the module saves the first error code
generated. The displayed error is deleted first and then the next error is
displayed.
In case of fatal error where LED blinks every 0.2 sec., recycle the power
(OFF -> ON) to delete the error.
In case of non-fatal error where LED blinks every 1 sec., the error can be
removed without recycling the power (OFF -> ON) and the module can
keep operating.
In case of non-fatal error where LED blinks every 1 sec, the parameter
value causing the specific error is not set on the module, and the existing
parameter value is kept as it is.