Code
Parameter
P2.6
Parity type
P2.7
Communication time out
P2.8
Reset communication status
When OPTBH board has been installed, the comm.-parameters are as follows
P2.1
Sensor 1 type
P2.2
Sensor 2 type
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
Table 39. System parameters.
Min
Max
Default
0
2
0
813
0
255
10
814
0
1
0
815
0
6
0
14072
0
6
0
14073
ID
Note
0 = None
1 = Even
2 = Odd
The Stop Bit is 2-bit when Parity type is 0 = None;
The Stop Bit is 1-bit when Parity type is 1 = Even or 2 = Odd
0 = Not used
1 = 1 sec
2 = 2 secs, etc
0 = No Sensor
1 = PT100
2 = PT1000
3 = Ni1000
4 = KTY84
5 = 2 × PT100
6 = 3 × PT100
0 = No Sensor
1 = PT100
2 = PT1000
3 = Ni1000
4 = KTY84
5 = 2 × PT100
6 = 3 × PT100
93