Voltage limiter enable
Voltage limiter function addresses problem with very high DC-link voltage
ripple with 1-phase drives when fully loaded. Very high ripple in DC-link volt-
age will transform to high current and torque ripple, which can disturb some
users. Voltage limiter function limits maximum output voltage to bottom
of DC-voltage ripple. This reduces current and torque ripple, but decreases
maximum output power since voltage is limited and more current is needed.
0 = disable,
1 = enable.