10.3
Frequency references
(Control panel: Menu PAR
Remote control place frequency reference selection
It defines the selected frequency reference source when the drive is remote
control. A second reference source is programmable in par. 3.12.
=
4.
Preset speed 0
=
5.
Keypad reference
=
6.
Fieldbus Reference
=
7.
AI1
=
8.
AI2
=
=
9.
PID 10.
AI1+AI2
=
11.
Motor potentiometer
Preset speeds 0 - 7
Preset speed 0 is used as frequency reference when P3.3 = 1.
Preset speeds 1 - 7 can be used to determine frequency references that are
applied when appropriate combinations of digital inputs are activated. Pre-
set speeds can be activated from digital inputs despite of the active control
place.
Parameter values are automatically limited between the minimum and max-
imum frequencies. (Par. 3.1 and 3.2).
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
P3)
Preset speed 1
Preset speed 2
Preset speed 3
Preset speed 4
Preset speed 5
Preset speed 6
Preset speed 7
Motor potentiometer ramp
Motor potentiometer reset
P3.13 is the speed variation ramp when motor potentiometer reference is
increased or decreased.
P3.14 tells under which circumstances the potentiometers reference should
be reset and start over from 0 Hz.
P5.12 and P5.13 sets which digital inputs increase and decrease the motor
potentiometers reference.
Table 50. Preset speeds 1 - 7
Speed
Preset
speed B2
×
×
×
×
0 = No Reset
1 = Reset if stopped
2 = Reset if powered down
Preset
Preset
speed B1
speed B0
×
×
×
×
×
×
×
×
112