Code
Parameter
P18.2 Fire mode frequency select
P18.3 Fire mode frequency preset
P18.4 Fire mode activation close
P18.5 Fire mode activation open
P18.6 Fire mode reverse
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
Table 21. Quick setup parameters.
Min
Max
Unit
0
Varies
P3.1
P3.2
Hz
0
Varies
0
Varies
0
Varies
Default
ID
0
1617
Fire mode frequency preset
NOTE! This parameter will be locked
when fire mode is active. To change
the parameter you have to disable fire
mode.
8,00
1598
Fire mode frequency preset
NOTE! This parameter will be locked
when fire mode is active. To change
the parameter you have to disable fire
mode.
6
1619
Digital input normal close
As parameter 5.1
NOTE! This parameter will be locked
when fire mode is active. To change
the parameter you have to disable
fire mode.
0
1596
Digital input normal open
As parameter 5.1
NOTE! This parameter will be locked
when fire mode is active. To change
the parameter you have to disable
fire mode.
0
1618
Reverse command of rotation direction
while running in fire mode. This DI has
no effect in normal operation.
As parameter 5.1
NOTE! This parameter will be locked
when fire mode is active. To change
the parameter you have to disable
fire mode.
Note
59