9.1.2
Start / stop setup (Control panel: Menu PAR
Code
Parameter
P2.1
Remote Control Place 1 Selection
P2.2
Start function
P2.3
Stop function
P2.4
I/O Start / Stop logic
P2.5
Local / Remote
P2.6
Keypad control direction
P2.7
Keypad stop button
P2.8
Remote Control Place 2 Selection
P2.9
keypad button lock
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
P2)
Table 23. Start / stop setup.
Min
Max
Unit
Default
0
2
0
1
0
1
0
4
0
1
0
1
0
1
0
2
0
1
ID
Note
0 = I/O terminals
0
172
1 = Fieldbus
2 = Keypad
0 = Ramping
0
505
1 = Flying start
0 = Coasting
0
506
1 = Ramping
0
300
I/O control
signal1
0 = Forward
1 = Fwd(edge)
2 = Fwd(edge)
3 = Start
4 = Start(edge)
0
211
0 = Remote control
1 = Local control
0
123
0 = Forward
1 = Backward
1
114
0 = Inactive
1 = Active
0 = I/O terminals
0
173
1 = Fieldbus
2 = Keypad
0 = unlock all keypad button
0
15520
1 = Loc/Rem button locked
I/O control
signal2
0 = Reverse
1 = Inverted Stop
2 = Bwd(edge)
3 = Reverse
4 = Reverse
65