Honeywell HVAC232 Series Applications Manual page 91

Table of Contents

Advertisement

Code
Parameter
P18.3
Fire mode:
frequency preset
P18.4
Fire mode activation:
close
P18.5
Fire mode activation:
open
P18.6
Fire mode:
reverse
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
Table 38. Fire mode.
Min
Max
Unit
Default
P3.1
P3.2
Hz
8.00
0
Varies
0
Varies
0
Varies
ID
Note
1598
Fire mode frequency preset
NOTE! This parameter will be locked when password for
fire mode is activated (not in the test mode), and not
only when fire mode input is set. To change the parame-
ter you have to disable fire mode.
6
1619
Digital input, if fire mode is enable or in test mode then when
digital input is closed, fire mode will be active.
As parameter 5.1
NOTE! This parameter will be locked when password for
fire mode is activated (not in the test mode), and not
only when fire mode input is set. To change the parame-
ter you have to disable fire mode.
0
1596
Digital input, if fire mode is enable or in test mode then when
digital input is open, fire mode will be active.
As parameter 5.1
NOTE! This parameter will be locked when password for
fire mode is activated (not in the test mode), and not
only when fire mode input is set. To change the parame-
ter you have to disable fire mode.
0
1618
Reverse command of rotation direction while running in fire
mode. This DI has no effect in normal operation.
As parameter 5.1
NOTE! This parameter will be locked when password for
fire mode is activated (not in the test mode), and not
only when fire mode input is set. To change the parame-
ter you have to disable fire mode.
91