Honeywell HVAC232 Series Applications Manual page 86

Table of Contents

Advertisement

Code
Parameter
P14.7
P gain
P14.8
I time
P14.9
D time
P14.10
Error inversion
P14.11
Sleep minimum frequency
P14.12
Sleep delay
P14.13
Wake up level
P14.14
Sleep setpoint boost
P14.15
Setpoint boost time
P14.16
Sleep maximum loss
P14.17
Sleep loss check time
P14.18
Process unit source select
P14.19
Process unit decimal digits
P14.20
Process unit minimum value
P14.21
Process unit maximum value
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
Table 35. PID control parameters.
Min
Max
Unit
0,0
1000,0
%
0,00
320,00
s
0,00
10,00
s
0
1
0,00
P3.2
Hz
0
3600
s
0,0
100,0
%
0,0
50,0
%
0
60
s
0,0
50,0
%
1
300
s
0
5
0
3
0,0
P14.21
P14.20
3200,0
Default
ID
Note
100,0
118
Proportional gain
10,0
119
Integrative time
0,00
132
Derivative time
0 = Direct
0
340
1 = Inverted
25,00
1016
Threshold for enter sleep
30
1017
Delay for enter sleep
90
1018
Threshold for exit sleep
10,0
1071
Referred to setpoint
10
1072
Boost time after P14.12
5,0
1509
Referred to feedback value after boost
30
1510
After boost time P14.15
0 = PID feedback value
0
1513
1 = Output frequency
2 = Motor speed
3 = Motor torque
4 = Motor power
5 = Motor current
1
1035
Decimals on display
0,0
1033
Process min value
100,0
1034
Process max value
86