Parameter Organisation; Motor Management Parameters - ABB UMC100-FBP Technical Description

Fieldbusplug
Hide thumbs Also See for UMC100-FBP:
Table of Contents

Advertisement

Universal Motor Controller
UMC100-FBP
Technical Description

Parameter Organisation

The UMC parameters are described in groups relecting the major function blocks of the UMC. The ig-
ures in braces (e.g. 1.1) provide the link the menu strucutre i.e. where it is displayed.
Motor Management lists all parameters related to motor management i.e. starting and stopping the mo-
tor and the control function
Protection lists all parameters related to the motor itself (e.g. nominal current) and the motor protection
functions
Communication lists parameters related to the ieldbus communication
IO Module lists all parameters related to the optional IO expansion modules
Display lists all parameters directly related to the LCD panel
Function block lists all parameters related to a speciic function block.
The column "Adjustable via" shows the possible options to adjust a parameter. "All" means the parameter
can be set via UMC100-PAN, GSD-PDP, GSD-PDQ, EDS CANopen, EDS DeviceNet and PBDTM.
Otherwise the available options are listed.

Motor Management Parameters

Pa-
Parameter
ra-
me-
ter
General motor management parameters
0
Control function Deines the type of starter function
1
Rev lock-out
time
4
YD changeover
mode
5
YD starting
time (Time Limit
Actuator)
7
Fault output
UMC100-FBP
Description, Explanations
Interlocking time before a start com-
mand in the opposite direction is ac-
cepted
The UMC switches from star to delta
either after a deined time or if the motor
current has decreased to 90% of I
Time switching from star to delta. If the
changeover mode is set to 'current' this
time deines when the motor current
must be below 90% of Ie.
Deines the maximum travel time from
one end position to the opposite end
position.
Behaviour of DO or DO3 in the event of
a trip or fault.
- 104 -
Options
Transparent (1),
Overload relay (),
Direct starter (3),
Reverse starter (4)
Star-delta starter (5),
Pole-changing starter (7),
Actuator_1 (9),
Actuator_ (10),
Actuator_3 (11),
Actuator_4 (1)
1-55 s
Time (0),
Current (1)
e1
1s to 360s in steps of
0,1s.
Default: 60s
Unscaled: 10 ... 3600
Example: A value of 10
means 1s
Off (0),
Flashing DO (1),
On DO (),
Invert DO (3),
Flashing DO3 (4),
On DO3 (5),
Invert DO3 (6)
FieldBusPlug / Issue: 11.009
V 6
Adjust-
able via
All
All
All
All
All