Universal Motor Controller
UMC100-FBP
Technical Description
Parameter Organisation
The UMC parameters are described in groups relecting the major function blocks of the UMC. The ig-
ures in braces (e.g. 1.1) provide the link the menu strucutre i.e. where it is displayed.
•
Motor Management lists all parameters related to motor management i.e. starting and stopping the mo-
tor and the control function
•
Protection lists all parameters related to the motor itself (e.g. nominal current) and the motor protection
functions
•
Communication lists parameters related to the ieldbus communication
•
IO Module lists all parameters related to the optional IO expansion modules
•
Display lists all parameters directly related to the LCD panel
•
Function block lists all parameters related to a speciic function block.
The column "Adjustable via" shows the possible options to adjust a parameter. "All" means the parameter
can be set via UMC100-PAN, GSD-PDP, GSD-PDQ, EDS CANopen, EDS DeviceNet and PBDTM.
Otherwise the available options are listed.
Motor Management Parameters
Pa-
Parameter
ra-
me-
ter
General motor management parameters
0
Control function Deines the type of starter function
1
Rev lock-out
time
4
YD changeover
mode
5
YD starting
time (Time Limit
Actuator)
7
Fault output
UMC100-FBP
Description, Explanations
Interlocking time before a start com-
mand in the opposite direction is ac-
cepted
The UMC switches from star to delta
either after a deined time or if the motor
current has decreased to 90% of I
Time switching from star to delta. If the
changeover mode is set to 'current' this
time deines when the motor current
must be below 90% of Ie.
Deines the maximum travel time from
one end position to the opposite end
position.
Behaviour of DO or DO3 in the event of
a trip or fault.
- 104 -
Options
Transparent (1),
Overload relay (),
Direct starter (3),
Reverse starter (4)
Star-delta starter (5),
Pole-changing starter (7),
Actuator_1 (9),
Actuator_ (10),
Actuator_3 (11),
Actuator_4 (1)
1-55 s
Time (0),
Current (1)
e1
1s to 360s in steps of
0,1s.
Default: 60s
Unscaled: 10 ... 3600
Example: A value of 10
means 1s
Off (0),
Flashing DO (1),
On DO (),
Invert DO (3),
Flashing DO3 (4),
On DO3 (5),
Invert DO3 (6)
FieldBusPlug / Issue: 11.009
V 6
Adjust-
able via
All
All
All
All
All