ABB UMC100-FBP Technical Description page 127

Fieldbusplug
Hide thumbs Also See for UMC100-FBP:
Table of Contents

Advertisement

Universal Motor Controller
UMC100-FBP
V 6
Technical Description
Digital Inputs DX111
Number of digital inputs
Supply for digital inputs
Isolation
Input signal bounce suppression
Signal 0 range including ripple
Signal 1 range including ripple
Input current per channel (4 V DC)
Input resistor to 0 V
Cable length
Digital Inputs DX122
Number of digital inputs
Supply for digital inputs
Isolation
Input signal bounce suppression
Signal 0 range including ripple
Signal 1 range including ripple
Frequency range
Input current per channel (30V AC)
Analogue Output
Type of connection
Conigurable output range
Cable shielding
Max. output voltage
Accuracy
Max. output load
Min. output load
Resolution
Short-circuit-proof
Open-wire detection
Short-circuit detection
Isolation
FieldBusPlug / Issue: 11.009
8 externally supplied, isolated inputs
Type 1 accord. to EN 61131-1
1DI0 ... 1DI4 with common root 1DIZ
DI5 ... DI7 with common root DIZ
4 V DC
Yes
Typ. 6ms
-31. ... +5 V
+15 ... +31. V
Typ. 6.0 mA
3.9 kΩ
unshielded max. 600 m
shielded max. 1000 m
8 externally supplied, isolated inputs
Type  accord. to EN 61131-1
1DI0 ... 1DI4 with common root 1DIZ
DI5 ... DI7 with common root DIZ
110 V AC - 40 V AC
Yes
Typ. 0 ms
0 ... 40 V AC
74 ... 65 V AC
45 ... 65 Hz
Typ. 10 mA
-wire connection to display e.g. the motor current
on an analogue meter.
0-10mA, 0/4 mA - 0 mA, 0-10 V
Recommended for up to 30 m and outside the
switchgear cabinet; shielding mandatory for
cables over 30 m
10V
< 5%
500 Ω (if conigured as current output)
1kΩ (if conigured as voltage output)
8 bit
Yes
Yes, if conigured as 0/4-0 mA output
Yes, if conigured as 0-10V output
No
- 17 -
UMC100-FBP

Advertisement

Table of Contents
loading

Table of Contents