Indicator
UMC self-test error
Actuator problem
IO module missing
Custom application error
(e.g. download incom-
plete)
IO module error
Aux1: Error or warning
triggered from auxiliary
function block input 0
Aux: Error or warning
triggered from auxiliary
function block input 1
Aux3: Error or warning
triggered from auxiliary
function block input 
Aux4: Error or warning
triggered from auxiliary
function block input 3
Aux5: Error or warning
triggered from auxiliary
function block input 4
Aux6: Error or warning
triggered from auxiliary
function block input 5
Multifunction input 0
Multifunction input 1
Multifunction input 
Cooling time running
Parameter out of range
FieldBusPlug / Issue: 11.009
Code
Source / Root Cause
14
Electronics
15
Load side mechanics
16
Electronics, Wiring
17
Coniguration
18
Electronics
19
User-deined
0
User-deined
1
User-deined

User-deined
3
User-deined
4
User-deined
5
User-deined
6
User-deined
7
User-deined
45
Process, Load side
54
Electronics, Coniguration
- 97 -
Possible Cause / Suggested Action
Hardware fault detected
Replace UMC
Open/close time of actuator exceed-
ed because of tight valve or other
mechanical reasons.
Check runtime parameter and limit
and torque switch wiring
Communication cable not connected.
Cable break or IO module hardware
error.
An unrecoverable error was detected
while processing the custom applica-
tion (e.g. checksum error)
The version of application editor and
UMC are not compatible
A self-test error was detected in an
IO module.
Check the LEDs on the module
Replace the module
The digital input of an IO module has
created a trip/warning.
Reason depends on what you have
connected to the input.
Note: If the "AuxWarnFault" function
block is used in a different way than
in the predeined applications also
other inputs than the DX1xx can be
the fault source.
A multifunction input of the UMC has
triggered a trip.
The reason depends on what you
have connected to the input.
Motor was tripped due to thermal
overload. Restart is possible after
cooling time is over
Someone tried to write a parameter
which is outside the speciications
Check the parameter number that is
causing the problem and change the
value.
When writing parameters from within
a a PLC check your program.