Actuator 4
Open position via torque and limit switches, Closed posi-
tion via limit switch only
24V
DI0
12
13
Definitions and monitoring signals particular to the control functions Actuator 1,2,3 and 4
Input signals: Open and Closed inputs are active signals, torque input is a closed loop signal.
The two torque signals are connected in series. The discrete torque signal is created based on the previ-
ous direction of movement.
Remark:
If DI is not needed as fault input it can be connected to the link between the torque contacts to ind out
which torque signal is active.
Run-time Open <-> Closed: The Run-time limit (= Star-delta starting time) must be changed and should
be set according to actuator data. Setting the Run-time limit = 1 s disables the supervision.
Starting from Open or Closed: The limit switch has to open within the start monitoring time of 3 s.
Exceeding the time results in the fault signal Open limit switch 1 -> 0 not occurring within 3 s after the
Closed command. The start monitoring time can be extended.
A faulty torque signal in the intermediate position sets the internal fault signal. The motor is stopped and
can be started again
- after fault reset via ieldbus or other - AND -
- only in the opposite direction (previous direction is blocked).
After starting the torque signal must disappear within 0.5 s. Otherwise the internal fault signal is set
again. A fault reset and start in the opposite direction can be repeated as often as desired.
If after powering up a torque signal (0-signal) is present and neither an Open nor a Closed signal is
present it is presumed that the torque occurred during closing. The motor can be started:
- after fault reset via ieldbus or other - AND -
- only in the Open direction
FieldBusPlug / Issue:08.009
Limit switches
DI1
14
Open
Closed
DI0: Preparation for Open limit motor off
DI1: Motor off, start only in Open direction
Torque
DI3
DI3:
16
Motor off if prepared for Open off, start only
in Closed direction
Open,
Fault if not prepared or if during closing
Closed
Remark:
The limit switch Closed prepares the stop.
Torque closed stops the motor. Starting is
only possible in the opposite direction
The single torque signals in the telegram
- torque Open or torque Closed - are calcu-
lated based on the direction of movement
before the stop.