Dx1Xx Status Codes; Replacing A Umc100; Replacing A Dx1Xx Io Module; Requesting Support - ABB UMC100-FBP Technical Description

Fieldbusplug
Hide thumbs Also See for UMC100-FBP:
Table of Contents

Advertisement

Universal Motor Controller
UMC100-FBP
Technical Description

DX1xx Status Codes

Three LEDs show the module status. The following table explains the status messages.
Status
Green LED
On
Flashing
Flashing
On
On
Irrelevant

Replacing a UMC100

The UMC and the current transformer are calibrated together in the ABB factory. Therefore the UMC must
be completely replaced.
The UMC can be disconnected from the FieldbusPlug without disturbing the ieldbus communication and
the other slaves. The FieldbusPlug is supplied via the voltage conducted together with the bus lines. The
FieldbusPlug keeps the actual slave address and informs the control system that the connected device is
disconnected.
Set the parameters in the new UMC depending on your parameterisation concepts.
After mounting and connecting a new UMC, the communication starts up again.

Replacing a DX1xx IO Module

DX1xx modules are automatically parameterized by the UMC if the communication between UMC and IO
module has been established. No further user actions are required.

Requesting Support

If you need support we kindly ask you to contact your local ABB representative using the template provid-
ed at the end of this manual.
UMC100-FBP
Yellow LED
Red LED
On
On
Off
On
Off
Off
Off
Off
Flashing
Off
Flashing
Flashing
Explanation
Self-test during start-up
Communication with UMC was interrupted. Relay outputs
switched off.
Possible cause: Wiring between UMC and IO module broken.
Possible corrective measure: Check wiring and check that the
module was activated in the UMC coniguration.
Waiting for communication with UMC. Module is ready.
Possible cause: Wiring between UMC and IO module broken.
Possible corrective measure: Check wiring and check that the
module was activated in the UMC coniguration.
Cyclic data exchange with UMC. No diagnosis.
Cyclic data exchange with UMC. Diagnosis exists.
Hardware defect.
Possible corrective measure: Replace module.
- 100 -
V 6
FieldBusPlug / Issue: 11.009