ABB UMC100-FBP Technical Description page 96

Fieldbusplug
Hide thumbs Also See for UMC100-FBP:
Table of Contents

Advertisement

Universal Motor Controller
UMC100-FBP
Technical Description
Indicator
Phase imbalance
Locked Rotor
Thermal model reached
warning level
PTC overtemperature
PTC wiring problem
Check-back error
Motor current below low
current trip threshold
Motor current below low
current warning threshold
Motor current above high
current trip threshold
Motor current above high
current warning threshold
Earth fault (external or
internal sensor) above trip
threshold
Earthfault current above
warning threshold
UMC100-FBP
Code
Source / Root Cause

Supply side
Load side
Contactors
3
Load Side
4
Load Side
5
Load side
Environment
6
Summary message. See
detailed messages for
more information.
7
Summary message. See
detailed messages for
more information.
8
Process
Load side
Load side mechanics
9
Process
Load side
Load side mechanics
10
Load side
11
Load side
1
Load side electrical
13
Load side electrical
- 96 -
Possible Cause / Suggested Action
The current in one phase is below the
adjusted threshold.
Check supply side
Check for loose contacts
Check contact wear
The rotor is locked. Load too heavy
for motor.
Thermal model reached warning
level. If overload condition remains a
trip soon follows.
Check motor load condition
Check for mechanical problems
PTC element indicated that motor
temperature is too high
Check motor environment and load
conditions
See codes 83/84
See codes 80...8
Motor current is below user-deined
threshold e.g. motor running idle, dry
running pump, conveyer belt broken
...
Check motor load and motor / pro-
cess conditions. Wait until cooling
time is over.
Motor current is below user-deined
threshold e.g. motor running idle, dry
running pump, conveyer belt broken
...
Check motor load and motor / pro-
cess conditions
Motor current above threshold
caused e.g. by jammed equipment
Check process conditions (remove
blocking cause). Wait until cooling
time is over.
Motor current above user-deined
threshold.
Check motor load and motor / pro-
cess conditions.
Connection between one or more
phases and ground
Check wiring / motor (isolation prob-
lem)
See above