6. Message Flow between the Radio and Sensor

6.1 Start-up Mode

Radio On Power ON (or) Restart, requests for some initial information from the Sensor board,
using stack specific message ISA100_GET_INITIAL_INFO (0x1C). The Sensor responds with
ISA100_NOTIFY_DEVICE_INFO (0x83 command) section.
The Radio sends the ISA100_GET_INITIAL_INFO message continuously once every
1.6 seconds up to 50 seconds. During this time, the Radio expects the Sensor to send at least
battery power status using ISA100_NOTIFY_POWER_STATUS (0x82) command. If the
Sensor does not send ISA100_NOTIFY_DEVICE_INFO and
ISA100_NOTIFY_POWER_STATUS packets to the Radio in 50 seconds, the Radio assumes
low battery power status and proceeds further. After 50 seconds, the Radio goes to a normal
mode condition, and then the Sensor can send ISA100_JOIN_STATUS (0x0D) command
Radio to request for join status.

6.2 Normal Mode

In addition to initial notification of Power Status using ISA100_NOTIFY_POWER_STATUS
(0x82), the power status information have to be communicated to the Radio periodically every
minute or on a change of power supply status or both.
The Sensor has to keep querying for the join status every 30 seconds (ISA100_JOIN_STATUS:
(0x0D)) until it receives the ISA100_NOTIFY_JOIN (Join Status Data is 1) from the Radio,
informing the Sensor that the Radio has joined the network. When the Radio drops off from the
network, the Sensor is notified by the Radio by the same message ISA100_NOTIFY_JOIN
(Join Status Data is 0) and sensor resumes its request for join status.
For the Sensor to publish data over the network, it requires a contract. The Sensor has to request
for a contract using ISA100_CONTRACT_REQUEST. It takes a while for the Radio to receive
the contract details from the system manager. The Sensor keeps requesting for a contract
ISA100_CONTRACT_REQUEST every 5 seconds until the
ISA100_NOTIFY_ADD_CONTRACT message containing the contract details is received from
the Radio. Once the contract is details are received the AI and BI data will be published over the
network as per the publish period obtained from the contract details message. The Radio also
keeps the Sensor notifying the TAI time every 20 seconds and the RSSI and RSQI values
every 1 minute.