ISA100_GET_INITIAL_INFO
ISA100_ADD_UAP_ALARM
ISA100_NOTIFY_RESET_CMD
ISA100_NOTIFY_TAI_TIME
ISA100_NOTIFY_UAP_STATUS
ISA100_NOTIFY_POWER_STATUS
ISA100_NOTIFY_DEVICE_INFO
ISA100_NOTIFY_ALARM_REGEN_BEGIN
ISA100_NOTIFY_ALARM_REGEN_END
ISA100_NOTIFY_RSSI_RSQI
Initial Information Related Messages
ISA100_GET_INITIAL_INFO
On reset, the Radio requests the initial information from the Sensor as per the packet
format in the following table.
Sync
h
Byte
0x5A
Release Independent
April 2018
Packe
Packe
Packe
t
t
t
Lengt
Class
Type
h
0x04
0x30
0x1C
ISA100 Gen X Radio Module User's Guide
28
Get the initial information serial number
and device tag descriptor from the sensor.
30
Add alarm message received from UAP to
ARMO queue
120
Radio issues the command to reset the
UAPMO
121
Radio sends the TAI time to the sensor
board every 20 seconds
129
Read Request /Response for the UAP
status
130
Sensor sends power supply status to
radio
131
Sensor sends the serial number and
device tag description to the Radio
140
Radio issues Alarm regen to sensor when
system issues the Alarm recovery
141
Sensor generates Alarm Regen end when
all pending alarms are generated
151
Sensor gets the RSSI and RSQI value from
the device and updates in the LCS display
Packe
Packe
Checksum
t ID
t size
LSB
0x9C
0x00
XX
Honeywell
Checksu
m MSB
XX
35