CHAPTER 5 - COMMISSIONING AND
MAINTENANCE INSTRUCTIONS
Error
Code
72
5.5
Error
Code
69
68
67
66
65
Error Code Meaning
Calibration Gas Too High
The calibration gas too high message is
displayed during calibration when the
calibration gas is adjusted to a level above
the pre-configured level.
This would not be indicated under normal
local operation since the pre-configured
operational data of the Engineering Card
push-buttons will prevent this type of
adjustment.

System Errors

Error Code Meaning
Invalid Sub-Channel
Indicates a request has been received for
an invalid sub-channel address.
Printer Not Ready
Indicates that the serial device attached to
the engineering port is not able to accept
data.
Invalid Request
Indicates that an invalid request number
has been received.
Serial Communications Timeout
Serial communications has timed out.
Reset card by removing power to the card.
If problem persists, replace the card.
Failed Error
Failed to receive command or card selected.
Reset card by removing power to the card.
If problem persists, replace the card.
5 - 17
5701 Control System
S/W
Card
Fault
Status Signal
All
Active
No
S/W
Card
Fault
Status Signal
All
Active
No
All
Active
No
All
Active
No
All
Active
No
All
Active
No
Latch
No
Latch
No
No
No
No
No