System Errors - Honeywell 5704 Operating Instructions Manual

System 57
Table of Contents

Advertisement

MAN0448_Issue 13_ 01-2010
005704-M-5001 A03249
CHAPTER 5 - COMMISSIONING AND
MAINTENANCE INSTRUCTIONS
Error
Code
69
68
67
66
65
64
63
5.5

System Errors

Error Code Meaning
Invalid Sub-Channel
Indicates a request has been received for
an invalid sub-channel address.
Printer Not Ready
Indicates that the serial device attached to
the engineering port is not able to accept
data.
Invalid Request
Indicates that an invalid request number
has been received.
Serial Communications Timeout
Serial communications has timed out.
Reset card by removing power to the card.
If problem persists, replace the card.
Failed Error
Failed to receive command or card
selected.
Reset card by removing power to the card.
If problem persists, replace the card.
Timeout Error
Backplane command timed out.
Reset card by removing power to the card.
If problem persists, replace the card.
Slot Inactive Error
Backplane command sent to empty slot.
Reset card by removing power to the card.
If problem persists, replace the card.
5-16
5704 Control System
Software Card Fault latch
Version Status Signal
All
Active No
All
Active No
All
Active No
All
Active No
All
Active No
All
Active No
All
Active No
No
No
No
No
No
No
No

Hide quick links: