Honeywell 5701 Operating Instructions Manual page 105

Sieger system 57
Table of Contents

Advertisement

MAN0443.P65 Issue 13 Aug 04
05701-M-5001 A02279
CHAPTER 4 - INSTALLATION INSTRUCTIONS
Single Channel Control Card 4 - 20mA 05701-A-0301
Fitted with 4 - 20mA Sensor Drive 05701-A-0283
Searchline Excel Receiver
Current Source
Receiver Connections
Connections using a
DX100 Junction Box
BLUE B
ORANGE A
4
TB1
1
TB2
4
RED +24V
WHITE 4-20mA
BLACK 0V
GRN/YEL GND
Note: 1.
Where a sensor is earthed locally, either to the Earth Stud or
through the sensor casing or mounting, to avoid earth loops
the screen sheath of the cable should only be connected at
one end. ie. At the sensor or at the Interface/relay Card.
2.
The Searchline Excel analogue output is non isolated and is
factory configured as current sink or current source.
Connector and link settings are shown for current source
model only, contact Zellweger Analytics for other option.
Three Wire Control Card Current Sink, Transmitter Current Source Connection for
Connections using a
DVC100 Junction Box
4
BLUE
B
ORANGE
A
BLACK
0V
1
0V DC Supply
WHITE 4-20mA
4-20mA Output
4
+24V DC Supply
RED
24V
GND
GRN/YEL GND
1
+24V DC Supply
4-20mA Output
0V DC Supply
IS EARTH
Cable
Earth
Shield
Terminal
Instrument Earth
Searchline Excel (Signal Returned to 0V)
Relay/Field Interface Card
05701-A-0326
05701-A-0327
05701-A-0328
05701-A-0329
05701-A-0330
1
Arrows Indicate
Direction of Loop
Current Flow
Screened Cable
Control Cabinet
Connections
Rx (+24V)
Rx (SIG)
Rx (0V)
IS EARTH
Earth
4 - 42
5701 Control System
Cabinet
27
NS
29
01
S
Protective
Earth
(Instrument
or Clean
Earth)
Link Positions
28
LK12
LK10
LK7
LK3

Hide quick links: