Ê Place the GPGPU tray so that the system board connector of the riser (see
oval) is not damaged.
Ê Disconnect the I2C cable from the riser (see arrow).
Ê Remove four screws from the outside of the chassis in the order of
numbering (1 - 4).
Ê Remove the riser in a vertical motion out of the chassis.

10.9.3 Installing the GPGPU riser

Figure 229: Installing the riser (R)
Ê Insert the riser in a vertical motion in the chassis.
V
Ensure that the system board connector of the riser (see oval) is not
damaged.
Ê secure the riser with four screws from the outside of the chassis in the order
of numbering (1 - 4).
Ê Connect the I2C cable to the riser (see arrow).

10.9.4 Concluding steps

Perform the following procedures:
CX2550/60/70 M4
Upgrade and Maintenance Manual
GPGPU extension tray
347