Replacing Memory Modules; Preliminary Steps; Preparing A Memory Module - Fujitsu PRIMERGY CX2560 M4 Upgrade And Maintenance Manual

Server node
Hide thumbs Also See for PRIMERGY CX2560 M4:
Table of Contents

Advertisement

7.5.2

Replacing memory modules

Field Replaceable Unit
(FRU)
Tools: Phillips PH2 / (+) No. 2 screw driver
7.5.2.1

Preliminary steps

"Disabling the boot watchdog functionality of ServerView Operations
Ê
Manager" on page 73
"Shutting down the server node" on page 50
Ê
Ê Disconnect the tubes from the tube system of the rack, see the "RackCDU
Service Manual".
"Removing the server node from the server enclosure" on page 51
Ê
"Removing memory modules" on page 194
Ê
7.5.2.2

Preparing a memory module

Figure 91: Prepared memory module
Ê Stick the cooling pads on one or two sides of the memory modules, see
"Adhesive rules for the memory cooling pads" on page
I
For Japan
Spare parts of memory module have 2 cooling pads. Regardless of
the memory position, use 2 cooling pads when replacing memory
module.
CX2550/60/70 M4
Upgrade and Maintenance Manual
Main memory
Hardware: 15 minutes
Software: 5 minutes
199.
TM
201