16. Appendix 3 - Wiring Diagrams

16.7 DIM in Supervised Configuration

R
INL
Switch
R
INL
Switch
R
INL
Switch
R
INL
Switch
Notes:
1. For all shielded cables, shield (screen) should be connected to Earth tag bar/bus bar provided in Touchpoint Pro enclosure.
2. Switch can be manually operated push button or potential free contact.
3. Components marked with '*' in field for individual channels, R
3. Maximum current through closed contact limited to 15mA.
Recommended Cable:
2 Core, Twisted, Mesh Type
Shielded, 1.5mm
or 2.5mm
2
* 2.7KΩ
R
* 10KΩ
EOL
* 2.7KΩ
R
10KΩ
*
EOL
* 2.7KΩ
R
10KΩ
*
EOL
* 2.7KΩ
R
10KΩ
*
EOL
= 10KΩ / 0.25W / 1%, R
EOL
2
E
= 2.7KΩ / 0.25W / 1%.
INL
217
Touchpoint Pro
Operating Instructions
DIM Module
+
+24VDC
1
2
-
Channel 1
3
1.075 KΩ
0VDC
+
+24VDC
4
5
-
Channel 2
6
1.075 KΩ
0VDC
+
+24VDC
7
8
-
Channel 3
9
1.075 KΩ
0VDC
+
+24VDC
10
11
-
Channel 4
12
1.075 KΩ
0VDC

Advertisement