MAN0923_Issue 3_04/15
2. A list of all output channels is shown in order of channel ID. The channel ID, location tag and status
are shown
3. The list can be filtered by status – Fault, Inhibit, Warning or All
4. Select a channel. Depending on access level, a number of options are shown
Function
Access
Comment
Level
Inhibit
Engineer
Inhibits the channel. On an inhibited channel, this option is Clear Inhibit. See Normal Operation, Inhibit for
more information.
Force
Operator /
Option to force a relay output channel to its active state, or force an analogue output channel to a set mA
Engineer
level. On a forced channel, this option is Clear Force. See Maintenance Ch. 8.1 Testing the Touchpoint Pro
System for more information.
Note: Operator level access is required to Force a channel. Engineer level access is required to Clear Force.
7. Normal Operation
Figure 7.15 Outputs Screen
Figure 7.16 Outputs Screen with filter options
106
Touchpoint Pro
Operating Instructions