Specifications - Honeywell touchpoint Pro Operating Instructions Manual

Hide thumbs Also See for touchpoint Pro:
Table of Contents

Advertisement

MAN0923_Issue 3_04/15
This section contains basic information about the various Touchpoint Pro major equipment and assemblies.
Note: Power Supply Fluctuations are not to exceed ±10 % of nominal.
Note: All equipment in this manual is rated to +2000 m (6562 ft) altitude maximum.
10.1 Rack Mounted Equipment
All rack-mounted enclosures are Equipment Class 1 (grounded) and Installation Category 2.
This apparatus must be installed in a suitable enclosure which provides a Pollution
Cet appareil doit être installé en zone sure dans un boitier conforme au niveau 2 de
Rack mounted equipment (with or without a User Interface) shall only be installed in ordinary (safe area)
locations that provide a Pollution Degree 2 environment.
In addition the enclosure shall provide a level of protection of at least IP20 / Type 1 / Class 1 (grounded) to
mitigate the risk of electrical shock.
Power Supply ratings and ambient operating conditions for rack mounted installations are dependent on the
type and density of components that are installed. Also the upper Ta may be reduced dependent on internal
power dissipation. See individual component Rating labels for further details.
10.1.1 Touchpoint Pro User Interface only
Part Number
Material
Earthing Points
Dimensions (H x W x D)
Weight
10.1.2 19" 5U Rack Enclosure with User Interface
Part Number
Material
Earthing Points
Dimensions (H x W x D)
Weight

10. Specifications

WARNING
Degree 2 environment in ordinary (safe area) locations.
AVERTISSEMENT
pollution environnementale.
TPPR-V-0852
Mild Steel w. Membrane panel
M8 (main grounding) other M6
225 x 360 x 70 mm
4 Kg
TPPR-V-0602
Mild Steel
M8 (main grounding) other M6
483 x 222 x 110 mm
12 Kg
144