A.8.3

SINAMICS V60 faults and alarms

A.8.3.1

Overview

Alarm code
Description
A01
Unable to identify the power board
A02
Parameter validation error (CRC error, encoder type or parameter header invalid)
A03
Unable to write data to memory
A04
Control voltage is lower than 3.5 V.
A05
IGBT is detected overcurrent.
A06
Internal chip is detected overcurrent.
A07
Grounding short circuit occurs during drive initialization
A08
Signals from encoder phases U, V, W are detected all the same (all high or all low)
A09
TTL pulse error
A14
Software failure
A21
DC link voltage is higher than 405 V
A22
IGBT current exceeds the upper limit for 300 ms
A23
DC link voltage is lower than 200 V
A24
The difference between the position setpoint and the position actual value is greater than 1000 pulses
(1/10 rotation).
A41
Actual motor speeds is higher than 2300 rpm
A42
IGBT becomes overheating
A43
Following error exceeds the limit
A44
Motor load exceeds nominal motor torque
A45
Enable signal from Terminal 65 is lost during normal drive running
A.8.3.2

Common faults and alarms

Alarm
Background
code
A01
A02
A03
A04
A05
This alarm may occur
when the DC link is
connected
This alarm may occur
when the motor is run-
ning
A06
This alarm may occur
when the DC link is
connected
This alarm may occur
when the motor is run-
ning
Commissioning Manual
01/2017
Possible Cause
Power board is broken
The memory is damaged due to unexpected
power-off during data saving
Memory is damaged
The 24 V DC supply is abnormal
The drive is defective
There is a short-circuit between terminals
U, V, W and PE on the drive
Bad grounding
Motor insulation is broken
The drive is broken
There is a short-circuit between terminals
U, V, W and PE on the drive
Bad grounding
Motor insulation is broken
The drive is broken
Remedy
Replace the drive with a new one
Restore default parameters
Replace the drive with a new one
Check the 24 V DC supply
Replace the drive with a new one
Check the wiring
Make a correct grounding
Replace the motor with a new
one
Replace the drive with a new
one
Check the wiring or whether
the connection to U, V or W is
broken
Make a correct grounding
Replace the motor with a new
one
Replace the drive with a new
one