Note
Do not switch on the 24 VDC power supply for the SINUMERIK 808D ADVANCED before you finish setting the Drive Bus
addresses for all connected drives.
After setting a proper address, you must save the parameter and then restart the drive to apply your setting.
Note
After the Drive Bus communication is established for the first time, the internal communication parameters are automatically
changed and hence a dot appears on the display as follows:
You must perform a save operation to remove the dot.
Note
After the Drive Bus communication is established, the BOP is protected from any operation except clearing alarms and
acknowledging faults.
4.8.2

Switching on the SINAMICS V60 drive

Jog test
To implement Jog test for the SINAMICS V60 drive, proceed through the following steps:
1. Switch on the 24 VDC power supply to the drive, and the BOP displays "S-2".
2. Remove write protection of the drive by setting P01 = 1.
* The dot means that at least one parameter is changed without saving. To save the parameter changes, see Step 5
below.
3. Set the motor ramp-up/-down time constant P47 to 0. If there is no need to adjust the speed controller performance (P20
and P21), skip this step.
Commissioning Manual
01/2017
139