BOP display
Display
Example
8.8.8.8.8.8
.
S-2
S-3
S-4
S-Run
Para
Data
Func
S-Axx
S-LAxx
The subsequent alarms are displayed every two seconds.
1)
472
Description
Initializes the drive (drive self-
testing at power-on) and stay for
about one second during the pro-
cess
Precharges the drive (waiting for
the 220 V mains power)
Waits for drive enable from terminal
65 at X6
Waits for pulse enable from termi-
nals ENA+ and ENA- at X5
Drive is running properly
Editable parameter group
Read-only parameter group
Function group
Displays an alarm code associated
with a fault existent in the drive
system
Displays the first detected alarm
when more than one error occur at
the same time (The alarm number
always contains a letter "L".)
Preconditions for display of normal status
No error code appears
•
No power supply (24 VDC) fault
•
No power supply (24 VDC) fault
•
No alarm code appears
•
No error code appears
•
No power supply (24 VDC or 3 AC 220 V to 240
•
V) fault
No alarm code appears
•
No power supply (24 VDC or 3 AC 220 V to 240
•
V) fault
No alarm code appears
•
Terminal 65 has been enabled
•
No power supply (24 VDC or 3 AC 220 V to 240
•
V) fault
No alarm code appears
•
Terminals 65 has been enabled via an external
•
24 VDC power supply
Terminals ENA+ and ENA- have been enabled
•
-
-
-
-
1)
Commissioning Manual
01/2017