Setpoint Interface - X5; Digital I/O Interface - X6 - Siemens SINUMERIK 808D ADVANCED Commissioning Manual

Hide thumbs Also See for SINUMERIK 808D ADVANCED:
Table of Contents

Advertisement

4.5.5

Setpoint interface - X5

Interface
5V differential signal
Too high input voltage
may cause a damage to
the device.
4.5.6

Digital I/O interface - X6

Interface
To cancel an active alarm, apply a high level (+24 V) at this terminal.
1)
Commissioning Manual
01/2017
Pin
Signal
Description
name
1
+PULS
Pulse input setpoint +
2
-PULS
Pulse input setpoint -
3
+DIR
Direction of motor setpoint
+
4
-DIR
Direction of motor setpoint
-
5
+ENA
Pulse enable +
6
-ENA
Pulse enable -
Max. conductor cross section: 0.5 mm
If the drive is connected with a SIMATIC PLC, please make sure that the time delay between
PULS and DIR signals should be more than 16 μs.
Please ensure that all the terminals of interface X5 should be firmly wired, otherwise, it is forbid-
den to start the machine.
Pin
Signal
Description
name
1
65
Servo enable
2
RST
Alarm cancel
3
M24
Servo enable and alarm
cancel reference ground, 0
V
4
ALM1
Alarm relay contact 1 termi-
nal
5
ALM2
Alarm relay contact 2 termi-
nal
6
RDY1
Servo ready contact 1 ter-
minal
7
RDY2
Servo ready contact 2 ter-
minal
8
+24 V
Zero mark power supply
9
Z-M
Zero mark output
10
M24
Zero mark reference ground
0 V
Maximum conductor cross section: 1.5 mm
I/O type
Remark
I
Use the differential drive mode here
to transmit the pulse data correctly.
I
I
I
I
I
2
I/O type
Remark
I
+24 V = drive enable
0 V = drive disable
I
+24 V = high active
I
-
-
-
-
I
O
Pulse width: 2~3 ms
H = + 24 V, L = 0 V
I
2
1)
123

Advertisement

Table of Contents
loading